SECTION 14
Zone Response Type Definitions
••••••••••••••••••••••••••••••••••••••••••••••••••
In This Section
Zone Type Definitions
••••••••••••••••••••••••••••••••••••••••••••••••••
Zone Type Definitions
You must assign to each zone, a zone type, which defines the way in which the system
responds to faults in that zone. Zone types are defined below.
Type 00
Zone Not Used
Program a zone with this zone type if the zone is not used.
Type 01
Entry/Exit Burglary
#1
This zone type provides Exit and Entry Delays whenever the zone is
faulted if the control panel is armed in the AWAY or STAY mode.
When the panel is armed in the INSTANT or MAXIMUM mode, no
Entry Delay is provided. Entry Delay #1 is programmable from 0-99
seconds (field
35).
Exit Delay begins whenever the control is armed, regardless of the
arming mode selected, and is independently programmable from
0-99 seconds (field
34).
This zone type is usually assigned to sensors or contacts on doors
through which primary entry and exit will take place.
The SL150 will annunciate faster beeps during the last 10 seconds
of the exit delay.
Type 02
Entry/exit Burglary
#2
This zone type provides a secondary Entry Delay whenever the
zone is faulted if the panel is armed in the AWAY or STAY mode.
When the panel is armed in the INSTANT or MAXIMUM mode, no
Entry Delay is provided. Entry Delay #2 is programmable from
0-99 seconds (field
36).
The programmed Exit Delay (field
34) begins whenever the
control is armed, regardless of the arming mode selected.
This zone type is usually assigned to sensors or contacts on doors
through which secondary entry and exit will take place, and where
more time might be needed to get to and from the keypad (typically
used for a garage, loading dock, or basement door).
The SL150 will annunciate faster beeps during the last 10 seconds
of exit delay.
Type 03
Perimeter Burglary
This zone type gives an instant alarm if the zone is faulted when
the panel is armed in the AWAY, STAY, INSTANT, or MAXIMUM
mode. This zone type is usually assigned to all sensors or contacts
on exterior doors and windows.