SL150 Installation and Setup Guide
14–2
Type 04
Interior Follower
This zone type gives a delayed alarm (using the programmed
entry/exit time) if the entry/exit zone is faulted first. Otherwise this
zone type gives an instant alarm. This zone type is active when the
panel is armed in the AWAY and MAXIMUM modes. This zone
type is bypassed automatically when the panel is armed in
the STAY or INSTANT mode. This zone type is usually assigned
to a zone covering an area such as a foyer, lobby, or hallway
through which one must pass upon entry (after faulting the
entry/exit zone to reach the keypad to disarm the system).
Because this zone type is designed to provide an instant alarm if
the entry/exit zone is not violated first, it will protect an area in the
event an intruder hides on the premises before the system is
armed, or gains access to the premises through an unprotected
area.
Type 05
Trouble by Day/
Alarm by Night
This zone type will give an instant alarm if faulted when armed in
the AWAY, STAY, INSTANT or MAXIMUM mode. During the
disarmed state (day), the system will provide a latched trouble
sounding from the keypad (and a Central Station report, if desired).
This zone type is usually assigned to a zone that contains a foil-
protected door or window (such as in a store), or to a zone covering
a sensitive area such as a stock room, drug supply room, etc. This
zone type can also be used on a sensor or contact in an area where
immediate notification of an entry is desired.
Type 06
24-hour Silent
Alarm
This zone type sends a report to the Central Station but provides
no keypad display or sounding. This zone type is usually assigned
to a zone containing an emergency button.
Type 07
24-hour Audible
Alarm
This zone type sends a report to the Central Station and provides
an alarm sound at the keypad, as well as an audible external
alarm. This zone type is usually assigned to a zone that has an
emergency button.
Type 08
24-hour
Auxiliary Alarm
This zone type sends a report to Central Station and provides an
alarm sound at the keypad. (No bell output is provided). This
zone type is usually assigned to a zone containing a button for use
in personal emergencies, or to a zone containing monitoring devices
such as water or temperature sensors.
Type 09
Supervised Fire
(With Verification on
Zone 1)
This zone type provides a fire alarm on short circuit and a trouble
condition on open-circuit. The bell output will pulse when this zone
type is alarmed. This zone type is always active and cannot be
bypassed. This zone type can be assigned to a hardwired
zone, any zone in a wired zone Expansion Module, or
wireless zones. When used with zone 1 on the panel, 2-wire
smoke detectors can be used.
NOTE:
Only hardwired zone 1 can be programmed as a fire zone
in UL installations. However, any wireless zone can be
used as a fire zone.