Section 15 -Data Field Descriptions
15–3
✱
30 KEYSWITCH ENABLE (ZONE 7) 0
0 = disable; 1 = enable
A keyswitch can only be used on zone 7. See
Section 4–Basic Hardwired Zones
for installation details.
✱
31 SINGLE ALARM SOUNDING PER ZONE
(per armed period)
0
0 = no limit on alarm sounding per
zone
1 = limit alarm sounding to once per arming period for a given zone
UL installations: Must be 0 (no limit)
✱
32 FIRE SOUNDER TIMEOUT 0
0 = yes; fire sounder timeout after time programmed in field ✱33
1 = no fire sounder timeout; continue sounding until manually turned off
This control complies with NFPA
requirements
for temporal pulse sounding of
fire notification appliances.
Temporal pulse sounding for a fire
alarm
consists of the following:
3 pulses – pause – 3 pulses – pause – 3 pulses.
✱
33 ALARM BELL TIMEOUT 1
0 = no
timeout
1 = 4 min; 2 = 8 min; 3 = 12 min; 4 = 16 min
This field determines whether the external sounder will shut off after time
allotted, or continue until manually turned off.
UL installations: Must be set for a minimum of 4 min (option 1).
✱
34 EXIT
DELAY
9 | 9
0 –99 seconds
The system will wait the time entered before it sounds an alarm if the exit
door is left open after the system has been armed.
UL installations: Must be set for a maximum of 60 seconds.
✱
35 ENTRY DELAY 1 (zone type 01) 6 | 0
0–99 seconds
The system will wait the time entered before it sounds an alarm upon
entering.
UL installations: Must be set for a maximum of 20 seconds.
✱
36 ENTRY DELAY 2 (zone type 02) 9 | 0
0–99 seconds
The system will wait the time entered before it sounds an alarm upon
entering.
UL installations: Must be set for a maximum of 50 seconds
✱
37 AUDIBLE EXIT WARNING 1
0 = no exit warning sound
1 = provides exit warning sound when armed AWAY.
Warning sound consists of slow continuous beeps until last 10 seconds, when
it changes to fast beeps. The warning sound will end at the termination of
Exit time.