SL150 Installation and Setup Guide
17–4
02 Start: Zn Typ
Not Used 00
If a zone type or system operation will be used to START the device
action, enter the appropriate 2-digit code (see table that follows). If
not, enter 00.
Press
✱
to continue.
CHOICES FOR ZONE TYPES
00 = Not Used 05 = Trouble Day/Alarm Night 10 = Interior w/Delay
01 = Entry/exit #1 06 = 24-Hr Silent 14 = Carbon Monoxide
02 = Entry/exit #2 07 = 24-Hr Audible 15 = Medical
03 = Perimeter 08 = 24-Hr Aux 24 = Silent Burglary
04 = Interior Follower 09 = Fire 64 = One-button Page
CHOICES FOR SYSTEM OPERATION
20 = Arming–STAY 36 = At Bell Timeout* 42 = System Battery Low
21 = Arming–AWAY 38 = Chime 43 = Comm Failure
22 = Disarming (Code + OFF) 39 = Any Fire Alarm 52 = Kissoff
31 = End of Exit Time 40 = Bypassing 58 = Duress
32 = Start of Entry Time 41 = AC Power Failure 65 = Any CO Alarm
33 = Any Burglary Alarm
* Use 0 (Any) at Disarming
02 Start:
0
Enter 0 for any.
Press
✱
to continue.
02 Stop: Zn List
No List 0
If a zone list will be used to Stop, or restore, the device action,
enter the zone list number 1, 2, or 3 (to be programmed in
✱
81
mode). If not used, enter 0.
Press
✱
to continue.
02 Stop: Zn Typ
Not Used 00
If a zone type or system operation will be used to Stop the device
action, enter the appropriate 2-digit code (refer to the
“
CHOICES
FOR ZONE TYPES
”
listed above). If not, enter 00.
Press the
✱
key to continue.
02 Stop:
0
Enter 0 for any.
Press
✱
to continue.
02 A EV ZL ZT
STT 0 0 0 00
This screen again displays a summary of the current device Start
(STT) programming. Press
✱
to continue.
02 A EV ZL ZT
ST – – 0 00
This screen again displays a summary of the current device Stop
(STP) programming. Press
✱
to continue.
02 X10 Device ?
0 = No, 1 = Yes 00
Enter 1 if you are using a Powerline Carrier device (
X10); if not,
enter
0
.
The display then returns again to the first screen so that the next
device
number to be programmed can be entered. Enter 00 to end
device programming.
Example of
Output Device
Programming
Assume that a lamp is to be turned on via a
Powerline Carrier
device
(
X10
) when any one of 3 specific zones are faulted, or when
any 24-hour auxiliary zone is faulted. Additionally, assume that you
want to be able to turn off the lamp manually without affecting the
Commentaires sur ces manuels